Question 1 · 3.2 Survey Existing Conditions
Per NFPA 13 (2022), the QR reduction for an existing system is:
Show the answer and where to find it
Answer: D. Permitted on wet systems only, up to 40%
QR reduction is wet-only, up to 40%. A (not permitted) is wrong. B (always 40%) ignores ceiling height. C (dry) is the opposite.
Find it: NFPA 13 (2022) §19.2.3.2.3.1 — QR reduction.
Question 2 · 3.3 Codes and Standards
Per NFPA 13 (2022), equivalent lengths are based on which C-value?
Show the answer and where to find it
Answer: B. C=120
Table normalizes to C=120. A (100) is dry. C (140) is cement. D (150) is copper.
Find it: NFPA 13 (2022) Table 28.2.3.1.1 — equivalent lengths.
Question 3 · 3.4 Sprinkler System Layout
Per NFPA 13 (2022), a 264-lb horizontal load resolved into a brace at 45° from vertical.
Axial force =
Show the answer and where to find it
Answer: D. 373 lb
Axial = horizontal ÷ sin(angle from vertical) = 264 ÷ 0.707 ≈ 373 lb. B (264) ignores the angle. C (305) divides by cos 30° — a different angle. A (187) multiplies by 0.707 instead of dividing.
Find it: NFPA 13 (2022) §18.5 — brace angle and axial load.
Question 4 · 3.4 Sprinkler System Layout
NFPA 13 (2022) seismic bracing. Zone of influence: 40 ft of 4-inch Sch 40 water-filled pipe at 16.4 lb/ft.
Wp =
Show the answer and where to find it
Answer: C. 754 lb
40 × 16.4 = 656; × 1.15 = 754 lb. A (590) uses a wrong lb/ft. B (656) forgot the 1.15 factor — the most common seismic hand-calc error. D (820) over-applies the factor.
Find it: NFPA 13 (2022) §18.5 — Wp with 1.15 factor.
Question 5 · 3.4 Sprinkler System Layout
Per NFPA 13 (2022), what must the water supply for a light hazard pipe schedule system provide?
Show the answer and where to find it
Answer: A. 15 psi residual at the highest sprinkler, 500–750 gpm at the riser base
Pipe schedule doesn't mean supply-free. NFPA 13's table sets light hazard at 15 psi residual, met at the elevation of the highest sprinkler, with 500–750 gpm at the base of the riser, hose included, for 30 or 60 minutes. D is the ordinary hazard row. B checks static pressure only. C skips the sprinkler flow.
Find it: NFPA 13 (2022) §19.2.2.1, Table 19.2.2.1; §19.2.2.5.1 — residual at the highest sprinkler.
Question 6 · 3.4 Sprinkler System Layout
Per NFPA 13 (2022), the hose stream allowance for Ordinary Hazard is:
Show the answer and where to find it
Answer: C. 250 gpm
OH = 250 gpm hose. B (100) is LH. D (500) is EH. A (0) omits hose.
Find it: NFPA 13 (2022) Table 19.2.3.1.2 — hose stream allowance.
Question 7 · 3.4 Sprinkler System Layout
Per NFPA 13 (2022), the deflector distance for standard spray pendent sprinklers under flat unobstructed ceilings is:
Show the answer and where to find it
Answer: B. 1–12 inches below the ceiling
1–12 inches below the ceiling deck. The head must sit inside the hot ceiling jet to operate quickly.
Find it: NFPA 13 (2022) §10.2.6.1 — deflector position below ceilings.
Question 8 · 3.5 Complex Standpipe System Layout
Per NFPA 14 (2019), when may the AHJ require hose connections beyond those at stairs and horizontal exits in a fully sprinklered building?
Show the answer and where to find it
Answer: C. When travel to the most remote part of a floor tops 200 ft
On a sprinklered floor, the AHJ can require added hose connections where the most remote part of the floor is more than 200 ft of travel from a required exit with a hose connection. On an unsprinklered floor the trigger is 150 ft (B). Big floor plates are where this bites: layout catches it, the calc prices it. A and D aren't triggers.
Find it: NFPA 14 (2019) §7.3.2 — Class I hose connection locations (additional connections).
Question 9 · 3.6 Fire Pump Unit Layout
Per NFPA 20 (2022), what's the minimum test header for a 1,000 gpm fire pump using 2½ in. hose valves?
Show the answer and where to find it
Answer: A. Four 2½ in. hose valves on a 6 in. header supply
NFPA 20's pump data table sets the minimum for a 1,000 gpm pump at four 2½ in. hose valves on a 6 in. header supply. Flow tests run the pump to 150% of rated, 1,500 gpm here, so count outlets from the table, not by feel. B is the 750 gpm row, C the 1,250 and 1,500 gpm rows, D the 500 gpm row.
Find it: NFPA 20 (2022) §4.28, Table 4.28(a); §4.22.3.1.2 — hose valve count.
Question 10 · 3.7 Water Storage Tanks
Per NFPA 22 (2018), the refill time for a fire tank shall not exceed:
Show the answer and where to find it
Answer: B. 8 hours
The supply has to fill the required fire volume in 8 hours or less. A (1 hr) is far tighter than required. C (24 hr) and D (48 hr) exceed the limit.
Find it: NFPA 22 (2018) §4.2.1.4 — 8-hour fill.
How ready are you for the real exam?
ForemanForge's readiness meter gives you one score for the NICET WBSL Level III: General Plans Preparation exam. It counts every question you answer in the lessons and practice, scores you on each work element in NICET's content outline, and weights each one by its share of the exam.
- Your score shows after 20 answered questions and moves as you study.
- It shows which work elements are pulling your score down, so you know what to study next.
- Timed exams count, and it won't read Exam Ready until you've scored 70% or better on a timed exam in the last 60 days.
- Building · under 60
- Borderline · 60–74
- Exam Ready · 75 and up
The score is an estimate of how you'd do on the exam, not a guarantee of passing. NICET doesn't publish a fixed pass mark.
Start studying for WBSL Level III: General Plans Preparation
The first lessons of every level in each track are free. Have an account? Log in
Keep going
- NICET WBSL Level III: General Plans Preparation exam guide: what's on the exam, how it runs and which books you can bring.
- NICET Water-Based Layout Level I practice test
- NICET Water-Based Layout Level II practice test
- NICET WBSL Level III: Hydraulics and Water Supply Planning practice test
All NICET exam guides (Water-Based Systems Layout and the other programs ForemanForge covers)